By Andrew Eriksen

from left to right: ROMEX 12/2, ROMEX 12/3, EMT conduit,
IMC conduit, MC 12/2
Modern buildings have electrical wiring in all walls, and often in
ceilings and floors as well. As
electricity runs through the cables to be consumed elsewhere, an
electromagnetic field [EMF] is generated. This field surrounds the cable in its
entire length and becomes weaker with increasing distance to the cable. Electromagnetic fields are bothersome to
some individuals and can be measured by a gaussmeter.
When wiring a new building, or upgrading an existing building, it may be
prudent to choose a type of cable that emits less EMF, but which one to choose?
To find out, a selection of cables and metal conduits were purchased.
Only types that are widely available and in general use in the United States
were chosen. The cables tested were:
l
ROMEX 12/2 (2-conductor, AWG 12)
l
ROMEX 12/3 (3-conductor, AWG 12)
l
MC 12/2 (flexible metal-clad,
2-conductor, AWG 12)
The conduits tested were:
l
EMT - lightweight steel conduit
l
IMC - heavy steel conduit
The AWG 12 thickness of the wires were chosen, as they are used for
household wiring carrying up to 20 amps.
A Wiring Primer
In the electrical trade, the
grounding wire is always present in a cable and is not counted as a
conductor. A “2-conductor cable” thus
has three wires inside – a black one for the phase, a white for the neutral,
and a bare copper wire for the ground.
In some cases, the ground wire is green instead of bare.
A 3-conductor cable has one
additional wire, which is usually red.
This type of cable is commonly used for bringing two-phase (230 volt)
electricity to electrical stoves, clothes dryers and water heaters. It can also be used for lighting circuits
with two switches, such as in each end of a hallway.
Test setup
A combination of cables and
metal conduit were tested under identical conditions. To provide a test load, a 1380 watt space heater of brand
Intertherm (now SoftHeat) was placed approximately 20 feet away.
The metal conduits tested
were sold in 10-foot sections, but we used six-foot samples due to
transportation restrictions. The
measurements were done at the middle of the conduit. In all tests, the ground wire in the cable was connected to the
ground in the wall outlet, as it normally would be.
The ROMEX 3-conductor cable
tested was used without connecting the extra wire to
anything. It
was not tested whether connecting it to the ground would be helpful. Doing
so would violate the National Electric Code, which is
very specific about the color codes, and forbids running wires in parallel.
To limit outside interference
with the test, a specially shielded outlet was used, while the breakers were
off to all the other outlets within
twenty feet. The outlet used had
regular wiring inside EMT metal conduit, which went all the way back to the
breaker box.
The EMF levels were measured
by a gaussmeter of the TriField brand, produced by Alpha Labs in Utah. The
TriField meter was outfitted with the optional external probe that makes it one
hundred times more sensitive and able to pick up EMF down to 0.01 milligauss.
The 120 volt AC power in the
building did have some overlying static (“dirty power”) which could be picked
up with an AM radio. This static was
present whether any
current was running or
not. It appeared to come from the
outside of the building and this was
deemed not to be a problem for this comparison.
Results
The results from the
gaussmeter readings are shown in Table 1.
It is clear that the 3-conductor ROMEX wire (ROMEX 12/3) is vastly
superior to the 2-conductor (ROMEX 12/2).
This is due to the fact that the individual wires inside the cable
happen to be twisted around each other.
This effect is used in wires for computer networks and long telephone
cables, so it was not a surprise that it also worked well here.
What was surprising was that
the ROMEX 12/3 cable also is superior to the other cable combinations tried,
i.e. the flexible metal-clad cable (MC 21/2) and when the ROMEX 12/2 was put in
metal conduit and even when put in the heavy duty IMC conduit.
When the ROMEX 12/3 cable was
further shielded by EMT conduit, the
radiation level become so low that it only measured 0.4 milligauss directly on
the surface of the conduit.
Table 1 : Distance in inches
from cable for specific EMF levels
|
|
1 milligauss (0.1 microtesla) |
0.2 milligauss (0.02 microtesla) |
0.01 milligauss (1 nanotesla) |
|
ROMEX 12/2 |
10.5 |
18.5 |
37 |
|
ROMEX 12/2 in EMT |
3 |
6.5 |
25 |
|
ROMEX 12/2 in IMC |
2 |
5 |
15 |
|
ROMEX 12/3 |
0.6 |
1.7 |
3.3 |
|
ROMEX 12/3 in EMT |
-- |
0.7 |
2 |
|
MC 12/2 |
1.5 |
2.3 |
3.7 |
Conclusion
If wanting to wire a house
for lower EMF levels, using the 3-conductor twisted ROMEX 12/3 (or any other
suitable AWG size) is clearly a good choice.
It is about ten times as good as the standard 2-conductor ROMEX wiring.
The extra cost of using a
3-conductor cable is minor; it just costs somewhat more due to having more
copper in it. The price was very close
to the cost of the metal-clad MC cable, and much cheaper than using the rigid
metal conduits (EMT and IMC) as they are much more labor intensive to install.
It is only when combining the
3-conductor cable with a metallic conduit that even better results are
possible. Whether going this route is cost-justifiable must depend on the
project; in most cases it probably is not.
Putting the 3-conductor cable
in metal conduit may be a violation of the National Electric Code, NEC, even if
one wire is never used (the reason is that the extra wire could later carry
more power, which could generate more heat, which is the basis for the
NEC). Discuss the project with the
local building inspector.
An alternative to using the
3-conductor cable is to convert a 2-conductor cable by twisting it. This would
be a little cheaper and should not cause any potential issues with the building
inspector.
The tested 3- conductor ROMEX
cable did a full turn of the wires inside it for every
four inches (10 centimeters)
of running cable. This twist could be
duplicated by hand –
perhaps by using a variable-speed (low speed ) power
drill with a bent nail in the chuck to hold the cable. A non-electric set up should also be
possible.
Twisting the cable more than
once per four inches may improve the
shielding effect. The author has
not tested these possibilities.
A Comment for the
Chemically Sensitive
Some manufacturers of ROMEX
type cables add a slippery coating on the surface of the cables. This coating makes it easier to pull the
cable through a conduit, but it can be bothersome to sensitive
individuals. The author tried to leave
a sample in the desert sun for one month, but it was still bothersome.
Cables made by Southwire have
this coating, which is called SIMpull.
Another manufacturer, Encore,
does not use such a substance.
If the local building supply store only stocks ROMEX with this coating,
try an electrical supply store.